- Filling and venting of the suction-side pipework including the pump before commissioning.
- Avoiding air entrainment during pump operation (aeration will result in break-down of suction capability).
- Avoiding drainage of suction-side piping on standdown of pump by providing and installing a footvalve (danger of leakage due to dirt particles).
Suction Head With Non-Selfpriming Centrifugal Pumps
That means that the local atmospheric pressure pb is higher than the sum of net positive suction head HH and vapour pressure pv; the inlet pressure is thus no longer required. This interrelation is based on the drastic reduction of the vapour pressure of cold water. In practice, that means:Pumps operating at a negative minimum inlet pressure Hreq are capable of creating a suction lift (not self-priming).The suction capacity is approximately equal to the level of the negative minimum inlet pressure minus 1m safety factor.As pumps normally used in conjunction with building services are generally not of selfpriming characteristics, the following conditions for suction lift operation must be met: