Editorial: The Importance of Default Position in a Valve

27.10.2022
The illustration shows two pressure control valves. These are very similar but for the fact that one is normally-open and the other is normally-closed. The primary difference between the valves is the location of main orifice in relation to the spring, piston, and valve seat (or seal). Because these valves use liquid pressure to automatically overcome the pre-set spring force, the liquid moves the normally-closed valve to open, and the normally-open valve to close.
Editorial: The Importance of Default Position in a Valve

Image source: Plast-O-Matic Valves, Inc.

Normally-Closed Valves, Normally-Open Valves, Fail-to-Position Valves
Commonly known as “default position,” actuated or automatic valves that revert to a pre-determined position after the actuating force is removed are often referred to as “fail-safe” valves. The most common type is “fail-safe normally-closed.” “Fail-safe normally-open” valves are much less common, but are equally important. These are often found in cooling systems, or are used where flow is shut off only for periodic maintenance, etc.

Some valves, such as spring-loaded air actuated ball valves, can be converted between types.  There are also “fail-to-position” valves, which automatically move to a specific point, including “fail-freeze,” which will remain in place in case of a power failure or other event.

Normally-Closed Valves
An example of a normally-closed actuated valve is Plast-O-Matic’s Series EASMT Solenoid Valve. The valve opens when energized, and when that current is turned off, an isolated spring inside the valve forces it closed. The magnetic force of the solenoid coil must overcome the force of the spring to open the valve. Unless acted upon, the spring force keeps the valve closed. In the event of a power failure, the valve will automatically close.

An example of a normally-closed automatic valve is Plast-O-Matic’s Series CKM Check Valve. The valve opens when pressure is present at the inlet (or upstream) side. When that pressure ceases, the diaphragm inside the valve automatically forces it closed. The inlet pressure must overcome the force of the diaphragm to open the valve. Unless acted upon by inlet pressure, the diaphragm force keeps the valve closed. In fact, the valve closes before reverse flow can take place. (note that the above refers to Series CKM/CKS; most check valves, including ball type, are not normally-closed valves.)

Normally-Open Valves
An example of a normally-open valve is Plast-O-Matic’s Series ARV Air Release Valve. The valve is designed to close when water rises at system start up, and reopens automatically when the pump is shut off and the liquid drains from the piping. Unless liquid is present, gravity keeps the valve open.

Another example of a normally-open automatic valve is Plast-O-Matic’s Series PRHM Pressure Regulator. The valve is set to remain open at a predetermined pressure, and begins to close automatically when downstream pressure exceeds that predetermined pressure. When pressure downstream drops back to accepted levels, a spring inside the valve forces it back open. The downstream pressure must overcome the force of the spring to close the valve. Unless acted upon by excessive downstream pressure, the spring keeps the valve open (see illustration above).

Valves that can be Converted between Normally-Open and Normally-Closed
Air-Actuated, Spring-Return Ball Valves — Plast-O-Matic Series ABVS, ABRS & ABMS — are examples of valves that can be normally-open or normally-closed. In these valves, a rather large spring is used to force the actuator back to its original position, whether that is open or closed.

One of the advantages of a Plast-O-Matic Air x Spring Actuated Ball Valve is that it can be converted fairly easily between one type or the other. Because the spring forces the actuator one way or the other, it is simply a matter of redirecting what the spring acts upon.

With Series ABVS, this is done by backing off the adjusting cap (so the spring will not be compressed) then unscrewing the spring housing from one side of the actuator and moving it to the opposite side. (Likewise, the compressed air is swapped).

Converting Series ABRS & ABMS is a little more complex. The actuator must be removed from the valve (very easy to do), then a retaining ring on the bottom of the actuator must be removed (requires retaining ring pliers). The pinion shaft is then pushed out from the top, rotated 180º, then re-inserted. The actuator will then act upon the valve opposite the way it did before.

Valves with Programmable Fail-Safe Positions
Some valves have the capability to fail-safe to a variety of options. The CAFE NITRO electric actuator may be used on ball valves and butterfly valves, pre-set to fail-closed, fail-open, fail to a specific degree of open/closed, or fail-freeze as required by the application. The fail-safe position is determined by the user, selected via an on-board menu screen.

Choosing a Default Position
In most applications the default position is determined by the type of valve required. For the two types of pressure control valves shown in the photo above, backpressure/relief valves are generally normally-closed while pressure regulator/pressure reducing valves are generally normally-open. In some cases these default positions have little or no relevance to the application, particularly if either is used for continuous pressure control. In others, such as when a backpressure valve is used in chemical dosing to prevent siphon, default position is of foremost importance.

Default position tends to be more critical in on/off or modulated flow applications.  For example, on a filling line or fertilization system where overflow could be a problem, it might be essential to specify “normally-closed.” On the other hand, a process cooling application may need to default to “normally-open” to prevent overheating. These can become dangerous or exceedingly costly if default position is overlooked in processes featuring aggressive chemicals. If you have any questions concerning the most appropriate design for an unusual application, contact our technical group for assistance.

More articles on this topic

Hydrogen: A Déjà Vu Moment for Arlon 3000XT

20.07.2023 -

The key to new challenges is sometimes hidden in the past. Such is the case with equipment and processes needed to produce, store, and transport hydrogen. A major hurdle facing those looking to upgrade their equipment or design new equipment is: Lack of polymer materials capable of withstanding the extreme challenges inherent to the hydrogen environment.

Read more

AxFlow Norway Announces Acquisition of VA-Prosjekt Midt-Norge AS

03.07.2023 -

AxFlow Norway is pleased to announce the successful acquisition of VA-Prosjekt Midt-Norge, a renowned provider of turnkey solutions to municipalities in the field of water and wastewater infrastructure. The acquisition marks a significant milestone in AxFlow’s strategic expansion plan, reinforcing its commitment to delivering comprehensive and sustainable solutions to customers in Norway.

Read more

Editorial: How/When/Where to Specify Air Release & Degassing Valves

29.06.2023 -

An Air Release Valve is open when the system is depressurized. At start up, the liquid process forces most of the air in the pipeline to high points, where the ARV allows it to escape. Once liquid rises, the valve closes and will not allow anything – gas or liquid – to pass in or out. It will not vent gas as it occurs during daily operations. It will reopen only when the system is depressurized and liquid level drops.

Read more

TECHINDIA 2023

19.06.2023 -

TECHINDIA is a leading Business Exhibition on Engineering and Manufacturing. The 11th edition scheduled during 1-3 September 2023, at Bombay Exhibition Centre, Mumbai (India) will showcase the exhaustive range of innovations and technological refinements in the complete product segment of “Pumps, Valves & Compressors”, “Gears, Motors & Controls” and “Bearings, Shafts & Couplings” and other allied sectors.

Read more