Data Center Cooling – Satisfying Highest Demands on Performance and Reliability

29.08.2012

Servers have become an ever more important part in our daily lives because of the phenomenal growth in web hosting and cloud computing. Server reliability is crucial in sensitive industries like banks, insurance companies, major corporations, as well as for government agencies.

Data Center Cooling – Satisfying Highest Demands on Performance and Reliability

Heat exchanger / Chiller
(Image: Carrier)

Carrier France, a recognised supplier of energy-efficient cooling systems, has been relying on hermetic refrigerant pumps with canned motors made by Hermetic for years. The Carrier department "Advante3c" has compared several solutions regarding efficiency, reliability and space requirements for a current reference project.

One solution utilised air cooling, requiring 5000 m³ of air; the second used water at a volumetric flow rate from 75 to 100 m³/h. The third solution involved cooling with carbon dioxide at a volumetric flow rate of approx. 12m3/h. Following extensive analysis, Advante3c has opted for the third solution: cooling with CO2 as a refrigerant. The first two options were rejected due to the required space and the high risk associated with using water to cool a server room.

Hermetic-Pumpen GmbH was selected as refrigerant pump supplier to put this development into practise. Hence, a new pump for refrigeration applications was developed in close collaboration with Advante3c engineers. The CAM 30 series from Hermetic meets high expectations for performance, reliability, tightness, and the physical requirements for the utilisation of CO2. This pump features a maximum leakage rate of less than 1 gram of CO2 per year at a system pressure of 64 bars. Innovative materials provided the solution, especially where seals were concerned.

The special design of the pump within the so-called "Tandem" design ensures reliable cooling of the motor and effective degassing. With the extensive expertise of Hermetic-Pumpen GmbH in resolving complicated issues in the oil & gas industry, as well as chemical and refrigeration engineering applications, it was possible to successfully and quickly realise this solution-focussed design.

Technical data

Pump type: CAMV 30/3+0

Nominal pressure: PN 75 bars

Medium: CO2

Operating temperature: 15 °C

Vapour pressure: 52 bars

Motor output: 3 kW

Reliability according to Advante3c calculations: 99.88 %

More articles on this topic

Sulzer Pump Retrofit Secures Flare Knockout Pump Reliability

21.11.2023 -

To ensure the profitability of offshore oil and gas extraction, operators require equipment to perform reliably throughout long periods between maintenance intervals. When an international oil company (IOC) was experiencing short mean time between failures (MTBF) for its liquified petroleum flare knockout vessel pumps on an offshore platform in Malaysia, the business approached Sulzer for a pump retrofit to safeguard uptime.

Read more